Specification: HEW - Water to water heat exchanger |
| Item/Model |
HEW-800PTS |
HEW-2RPTS |
HEW-3RPTS |
Cooling
capacity |
KCAL/H |
3000 |
6000 |
9000 |
W |
3500 |
7000 |
10500 |
BTU/H |
12000 |
24000 |
36000 |
Temp.
controller |
A |
Fixed temperature control type (setting range 10~40°C) |
| B |
Differential temperature control type (tracing room/machine body temperature, setting range -10 ~ +10°C) |
| Power source |
3Φ 200 ~ 230V 50/60 Hz |
| Pump |
W |
750 |
750 |
2650 |
| Max. flow rate L/min |
50 |
50 |
100 |
| Max. liquid lift M |
40 |
40 |
50 |
| Minimum cooling water flow rate L |
40 |
| Liquid inlet diameter PT |
3/4" |
| Liquid outlet diameter PT |
3/4" |
| Cooling water Inlet diameter PT |
3/4" |
| Cooling water outlet diameter PT |
3/4" |
| Tank capacity |
45L |
Dimension
WDH mm |
490500795 |
|
|
| |
|
The above cooling capacity is based on the condition of liquid temperature of 22°C, cooling water source of 10°C. |
|
Specification: RW - Water cooled liquid cooler |
| Item/Model |
RW-3RPTS |
RW-4RPTS |
RW-5RPTS |
RW-7.5RPTS |
Cooling
capacity |
KCAL/H |
7000/9000 |
10000/12000 |
12500/15000 |
18600/22500 |
W |
8700/10500 |
11600/14000 |
14500/17500 |
21600/26100 |
BTU/H |
30000/36000 |
40000/48000 |
50000/60000 |
74000/89000 |
Temp.
controller |
A |
Fixed temperature control type (setting range 10~40°C) |
| B |
Differential temperature control type (tracing room/machine body temperature, setting range -10 ~ +10°C) |
| Power source |
3Φ 200 ~ 230V 50/60 Hz |
| Compressor Power W |
3690 |
4540 |
6210 |
8300 |
| Pump |
W |
845/1280 |
860/1510 |
| Max. flow rate L/min |
40/50 |
80/100 |
| Max. liquid lift M |
39/56 |
23/34 |
| Minimum cooling water flow rate L |
40 |
70 |
| Liquid inlet diameter PT |
3/4" |
1" |
1-1/4" |
| Liquid outlet diameter PT |
3/4" |
1" |
1-1/4" |
| Cooling water Inlet diameter PT |
3/4" |
1" |
1-1/4" |
| Cooling water outlet diameter PT |
3/4" |
1" |
1-1/4" |
| Tank capacity |
65L |
100L |
170L |
Dimension
WDH mm |
553×624×840 |
708×738×955 |
890×890×1255 |
|
|
| |
|
The above cooling capacity is based on the condition of liquid temperature of 22°C, cooling water source of 28 °C. |
| |